I    Home I     Latest News I   Recruitment I   Sharing our Knowledge I      Products I   How to Order I   Contact  I
Vent Vision Distributors of ventilation equipment across the UK
Fans Ventilation Heating from Vent Vision

Basics of Ventilation and Ventilation Requirements:

  1. Building Regulations
  2. Ventilation  Requirements
  3. How  to Plan Successful Ventilation
  4. Ventilation  Information
  5. System Calculator
  6. Understanding  the Problem of Condensation
  7. Basic  Units of Measurements

Documents to Download    Section  One - The Basics of Ventilation and Ventilation  Requirements.

Section  Two - Electrical Safety, Fan Types, Fan Laws  and Noise.

Documents  are PDF files. You will require Acrobat Reader to  view.

Information supplied by Vent Axia

www.vent-axia.com

Sharing Our Knowledge

Ventilation  Requirements

Air  change ratings

The  simplest method of determining the ventilation rate required  is to make use of the accumulated experience of the industry expressed in a table of air change rates. The volume in cubic metres (m3) of the space to be ventilated is calculated  and multiplied by the number of air changes per hour to  give the ventilation rate in m3 per hour. Division by 3.6 converts this to litres per second.

Ventilation  rate (litre/s) = Volume (m³) x air changes per hour / 3.6

The  table below gives a guide to the number of air changes generally  recommended. Provided air inlets and outlets are properly sited, the tabulated values will be sufficient for air movement requirements. They will also meet requirements for pollution and moisture removal, in typical examples of the accommodation  indicated, and heat removal requirements in temperate climates without heat sources.

However, particular installations should always be checked against  the following questions:

  • Are there specific bylaws or other legal requirements applicable in the locality?
  • Is the space expected to become so crowded that a higher  ventilation rate might be obtained by calculating on a per person basis?
  • Are  there abnormal sources of heat or fumes?
  • Is it desirable to provide a higher ventilation rate for  summer cooling?

Ventilation  rates per person

Each human being produces their personal quota of heat, water vapour, carbon dioxide and body odour. The ventilation requirement  for the last item will cover the needs of the other three  during the heating season. It is not sufficient merely to ensure an acceptable average freshness of atmosphere throughout the room; if people are crowded together by shortage of  space the average odour concentration must be reduced. This  means that the fresh air supply per person must increase  with the number of people in a room, and consequently the air change rate must increase. Recommended minimum fresh air supply.

Recommended  minimum fresh air supply

3m3

17 litre/s

20

6

11

6.5

9

8

3.2

12

6

1.8

These rates should be increased by a third if smoking is permitted or if there are doubts about standards of personal hygiene. If minimum legal requirements are specified, they are generally  about a third less. In contrast, as little as 1 litre/s will suffice to meet the strictly physiological needs of one person for oxygen supply and carbon dioxide limitation.

Further  calculations on air changes per hour will come later.

Consideration  of dust and odours in a normal office or workroom ventilation job can usually be ignored when preparing the scheme, as the rate of ventilation needed to give comfortable conditions based on temperature, humidity and air movement - 6 to 10  ACH - would be considerably higher than that required to  keep dust and odours down to a comfortable level - about  1 to 2 ACH.

Incidentally,  it is always advisable when dealing with a fairly crowded space (e.g. auditoria, dance halls) to give a quick check for the minimum air volume required by allowing 28m3/h per  person. This is to prevent body odours from becoming a nuisance.  Also the carbon dioxide content of the air, gradually increasing due to the CO2 exhaled from the lungs, should be prevented  from exceeding 10 parts per 10,000. This calculation is commonly used as the maximum CO2 concentration desirable in a closed occupied space.

Before you begin to think that this is getting rather complicated,  be reassured that in practice if we design a normal ventilation scheme to deal with temperature rise and air movement, the  remaining factors of humidity and purity (concentration of CO2, odours and dust) are taken care of. There are exceptions  to this in the case of humidity and dust, but they usually occur in the more specialised applications where the requirements  are either for full air conditioning with dehumidification  by refrigeration for humidity control, or for specific dust removal.

Vent Axia BSB Systemair Xpelair Elta Fans Premier Grilles Trox Actionair Ziehl-Abegg Baxi CleanAir